American Power Conversion

APC Smart-UPS 620VA 230V

Part Number: SU620INET
SU620INETSU620INET

Output

Output Power Capacity
390 Watts / 620 VA
Max Configurable Power
390 Watts / 620 VA
Nominal Output Voltage
230V
Output Connections
(1) IEC 320 C13
(3) IEC 320 C13
(2) IEC Jumpers

Input

Nominal Input Voltage
230V
Input Frequency
50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
IEC-320-C14 inlet
Input voltage range for main operations
160 - 286V
Input voltage adjustable range for mains operation
151 - 302V

Batteries & Runtime

Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
5.50 hour(s)
Replacement Battery
RBC™ Quantity
1
Typical Backup Time
at Half Load
15.7 minutes (195 Watts)
Typical Backup Time
at Full Load
5.5 minutes (390 Watts)
Runtime Chart

Communications & Management

Interface Port(s)
DB-9 RS-232
Control panel
LED status display with On Line : On Battery : Replace Battery and Overload indicators
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
N/A

Surge Protection and Filtering

Surge energy rating
320 Joules
Filtering
Full time multi-pole noise filtering : 0.7% IEEE surge let-through : zero clamping response time : meets UL 1449
Data Line Protection
RJ45 10/100 Base-T Ethernet protection

Physical

Maximum Height
168.00 mm
Maximum Width
119.00 mm
Maximum Depth
368.00 mm
Net Weight
12.27 KG
Shipping Weight
13.18 KG
Shipping Height
318.00 mm
Shipping Width
262.00 mm
Shipping Depth
508.00 mm
Color
Beige
Units per Pallet
40.00

Environmental

Operating Environment
0 - 40 °C
Operating Relative Humidity
0%
Operating Elevation
0-3000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
0.00 dBA
Online Thermal Dissipation
70.00 BTU/hr

Conformance

Regulatory Approvals
CE,EN 50091-1,EN 50091-2,GOST,VDE
Standard Warranty
2 years repair or replace,optional on-site warranties available,optional extended warranties available
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.